@openmep/hvac-domain
v0.4.0
Published
Deterministic round-duct sizing and supply/return/exhaust network propagation, as a library and a host-free CLI (openmep-hvac).
Maintainers
Readme
@openmep/hvac-domain
Deterministic, dependency-free ESM primitives for equal-friction round-duct sizing and supply, return, exhaust, and outside-air network propagation, plus a CLI that runs them on a JSON network with no editor or host. For agents, @openmep/mcp serves the same engine as MCP tools.
CLI
npx -p @openmep/hvac-domain openmep-hvac size network.json --pretty
npx -p @openmep/hvac-domain openmep-hvac duct --cfm 250 --role main --diameter-in 6
npx -p @openmep/hvac-domain openmep-hvac duct --cfm 900 --airflow return --width-in 14 --height-in 8size takes a JSON array of NetworkItems (or { "items": [...] }): equipment,
fittings, terminals with requiredCfm, and segments linked by connectedItemRefs.
A segment may describe its existing section, {"shape":"round","diameterIn":6} or
{"shape":"rect","widthIn":14,"heightIn":8}, and is then graded ok,
undersized, or oversized by ASHRAE circular equivalent. Each terminal's
airflowType (supply, return, exhaust, outside-air) picks the system; its
CFM follows same-system or unknown items to equipment and is sized with that
system's velocity caps. Output: summary, findings (missing-required-cfm:
error for supply, warning for other systems; no-equipment-path,
dangling-reference, mixed-system-segment, undersized, oversized), and
segments with system, CFM, role, recommended standard diameter, velocity, and
friction rate. Exit codes: 0, 1 with --fail-on-findings
and error findings, 2 for invalid input (NetworkInputError with a JSON path) or an
engine error. See examples/furnace-two-registers.items.json; the same document is
what openmep-pascal items emits from a Pascal scene.
Library
import { recommendDuctSegments } from "@openmep/hvac-domain";
const result = recommendDuctSegments(items); // or { airflowTypes: ["supply"] }sizeRoundDuct uses the ASHRAE friction-chart fit for galvanized round duct at
standard air. sizeDuctForAirflow applies role-based velocity caps for supply,
return, exhaust, or outside air; sizeSupplyRoundDuct is the supply convenience
wrapper. recommendDuctSegments returns sorted arrays suitable for JSON
serialization; recommendSupplyDuctSegments restricts it to supply.
sizeSingleDuct and sizeNetworkInput are the CLI's two commands as functions.
Engineering basis
The round-duct relation is Δp = 0.109136·Q^1.9/D^5.02, with pressure drop in
in. w.g. per 100 ft, airflow in CFM, and diameter in inches. It assumes standard
air (0.075 lb/ft³) and galvanized round duct roughness near 0.0003 ft. See the
official ASHRAE Duct Design chapter
for the standard-air friction chart and the 2025 ASHRAE Handbook—Fundamentals overview
for the current volume. Velocity caps are transparent recommendations, not
universal engineering limits.
Scope and limitations
- Network propagation covers terminals with a positive
requiredCfmin a classified system. Anunknownitem is shared by every system; if two systems load the same unclassified segment it is reported, not sized. - Recommendations are round. Existing rect and flat-oval sections are graded by ASHRAE circular equivalent; rectangular selection is not included.
connectedItemRefsare treated as an undirected graph because port direction is not represented.- Each terminal uses one lexically deterministic shortest compatible path to equipment. Loops are not hydraulically balanced and alternate paths do not share flow.
- The calculation excludes fitting losses, pressure summation, fan selection, diversity, static-regain design, elevation, non-standard air, code compliance, and engineering judgment.
Use the output as a transparent preliminary sizing primitive; validate final designs with a qualified mechanical engineer.
Development
npm run build --workspace @openmep/hvac-domain
npm run test --workspace @openmep/hvac-domainMIT licensed. See CONTRIBUTING.md and SECURITY.md.