@totemsdk/edge-bacnet
v0.1.0
Published
Edge runtime adapter for BACnet — building automation, HVAC, device properties
Maintainers
Readme
@totemsdk/edge-bacnet
Edge runtime adapter for BACnet — building automation, HVAC, device properties.
Install
npm install @totemsdk/edge-bacnetDesign
This package does not import node-bacnet or any BACnet stack. All BACnet behaviour is injected via BacnetTransportPort. The package handles device discovery, property read/write, COV subscriptions, and proof generation.
Quick start
import { createEdgeRuntime, createEdgeDevice, createCapabilitySet } from '@totemsdk/edge';
import { createBacnetGateway, createBacnetSensorBridge } from '@totemsdk/edge-bacnet';
import type { BacnetTransportPort } from '@totemsdk/edge-bacnet';
// 1. Implement BacnetTransportPort (e.g. using node-bacnet)
const transport: BacnetTransportPort = {
async init(deviceId, deviceName) { /* initialise BACnet stack */ },
async close() { /* shutdown */ },
async discoverDevices() { /* send Who-Is, collect I-Am responses */ return []; },
async readProperty(deviceId, objectType, objectInstance, propertyId) { /* read property */ return { objectType, objectInstance, propertyId, propertyName: '', value: null, dataType: '' }; },
async writeProperty(deviceId, objectType, objectInstance, propertyId, value, priority) { /* write property */ },
async subscribeCov(deviceId, objectType, objectInstance, lifetime) { /* subscribe to COV */ return { onChange(handler) { return () => {}; }, async cancel() {} }; },
onDeviceDiscovered(handler) { return () => {}; },
onError(handler) { return () => {}; },
};
// 2. Wire into Edge runtime
const runtime = createEdgeRuntime({
deviceId: 'bacnet-gateway-01',
capabilities: createCapabilitySet(['transport:bacnet', 'proof:create']),
ports: { /* proof port */ },
});
// 3. Create gateway with COV subscriptions
const gateway = createBacnetGateway({
runtime,
transport,
deviceId: 1001,
deviceName: 'TotemEdge',
covSubscriptions: [
{ deviceId: 2001, objectType: 'analogInput', objectInstance: 1, sensorId: 'zone-temp', lifetime: 300 },
{ deviceId: 2001, objectType: 'analogInput', objectInstance: 2, sensorId: 'zone-humidity', lifetime: 300 },
],
});
await gateway.start();
// COV notifications are automatically sent to the proof port
// 4. Discover devices
const devices = await gateway.discoverDevices();
console.log(devices.data?.devices);
// 5. Read a property
const value = await gateway.readProperty(2001, 'analogInput', 1, 85); // present-value
console.log(value.data?.value);
// 6. Write a property
await gateway.writeProperty(2001, 'analogOutput', 1, 85, 22.5, 8); // priority 8
// 7. Or use the sensor bridge for polling
const bridge = createBacnetSensorBridge({
runtime,
transport,
gateway,
bindings: [
{ sensorId: 'zone-temp', deviceId: 2001, objectType: 'analogInput', objectInstance: 1, propertyId: 85, intervalMs: 10000, dataType: 'temperature', unit: '°C' },
],
});
await bridge.start();Common BACnet object types
| Type | Description |
|------|-------------|
| analogInput | Sensor reading (temperature, pressure, etc.) |
| analogOutput | Actuator setpoint |
| analogValue | Configuration parameter |
| binaryInput | Switch/contact status |
| binaryOutput | Relay/valve command |
| multiStateInput | Mode selector |
| multiStateOutput | Mode command |
Common property IDs
| ID | Name | Description |
|----|------|-------------|
| 85 | presentValue | Current value |
| 77 | objectName | Human-readable name |
| 75 | units | Engineering units |
| 28 | description | Text description |
Capabilities
transport:bacnet— required for BACnet transport
License
MIT