@ya-modbus/driver-or-we-514
v0.1.12
Published
ORNO OR-WE-514 single-phase energy meter driver for ya-modbus
Maintainers
Readme
@ya-modbus/driver-or-we-514
ORNO OR-WE-514 single-phase energy meter driver for ya-modbus.
Device Information
- Manufacturer: ORNO
- Model: OR-WE-514
- Type: Single-phase energy meter, DIN rail (1 module), RS-485. Rated 5 A base, 100 A maximum. No multi-tariff function.
- Communication: Modbus RTU, holding registers (function code 03), big-endian, high word first for 32-bit values
- Default Settings:
- Address: 1
- Baud rate: 9600
- Parity: Even
- Stop bits: 1
- Data bits: 8
The defaults come from section 8.1 of the official manual. The page headers of the register list say "N81" (no parity); the manual says even, and a real meter runs 8E1.
Installation
npm install @ya-modbus/driver-or-we-514Usage
import { createDriver, DEFAULT_CONFIG } from '@ya-modbus/driver-or-we-514'
import { createRTUTransport } from '@ya-modbus/transport'
const transport = await createRTUTransport({
port: '/dev/ttyUSB0',
baudRate: DEFAULT_CONFIG.baudRate,
parity: DEFAULT_CONFIG.parity,
dataBits: DEFAULT_CONFIG.dataBits,
stopBits: DEFAULT_CONFIG.stopBits,
slaveId: DEFAULT_CONFIG.defaultAddress,
})
const driver = await createDriver({ transport, slaveId: DEFAULT_CONFIG.defaultAddress })
const values = await driver.readDataPoints(['voltage', 'active_power', 'total_active_energy'])
console.log(values)Data Points
All data points are read-only and are read on every poll.
| ID | Register | Type, scale | Unit |
| ----------------------- | ------------- | ------------- | ----- |
| frequency | 0x130 | UINT16, 0.01 | Hz |
| voltage | 0x131 | UINT16, 0.01 | V |
| current | 0x139-0x13A | UINT32, 0.001 | A |
| active_power | 0x140-0x141 | INT32, 1 | W |
| reactive_power | 0x148-0x149 | INT32, 1 | VAr |
| apparent_power | 0x150-0x151 | INT32, 1 | VA |
| power_factor | 0x158 | INT16, 0.001 | - |
| total_active_energy | 0xA000-0xA001 | UINT32, 0.01 | kWh |
| total_reactive_energy | 0xA01E-0xA01F | UINT32, 0.01 | kVArh |
The driver reads these registers in at most 8 requests per poll: 0x130 (2 registers), 0x139 (2), 0x140 (2), 0x148 (2), 0x150 (2), 0x158 (1), 0xA000 (2) and 0xA01E (2). A block is read only when one of its data points is requested. Wider reads are not tried on the meter.
Only these registers are verified on a real meter. Other registers in the list (system power values, multi-rate energy, demand, meter type) are not used.
Settings (0x110 address, 0x111 baud rate) are not exposed and the driver writes nothing to the meter.
Notes
- Power is in W, VAr and VA. The list gives 0.001 kW (kvar, kva) per count, which is 1 W (VAr, VA) per count. Checked on a real meter on 2026-10-13: 229.4 V x 7.571 A x power factor 0.999 = 1735, and register 0x140 returned 1736 W. Over the day the energy counter rose by 0.340 kWh, and the sum of the power values gave 0.340 kWh.
- Power factor is read signed. The list says INT. No negative value was seen on the real meter, so the sign handling is not checked on hardware.
- Values are not from one instant. The 8 requests are sent one after another, so a quickly changing load can make apparent power differ from the value calculated from active and reactive power.
Sources
- Register list "MODBUS Registers List" (PDF created 2019-03-22, no version; not found on the ORNO site, copy hosted by TapHome under the OR-WE-515 name): https://taphome.com/compatibility/devices/orno-or-we-515/manufacturer/register-description.pdf
- Official manual for OR-WE-512 / 514 / 515 (serial settings and defaults in section 8.1, no registers): https://www.partner.orno.pl/manuals/OR-WE-512,514,515_manual_EN.pdf