iobroker.bacnet-flex
v0.1.3
Published
ioBroker BACnet adapter with BACnet/IP, MS/TP router and BACnet/SC client modes
Readme
ioBroker BACnet Flex
BACnet adapter for ioBroker with BACnet/IP client and server modes, BACnet MS/TP access through an external BACnet/IP-to-MS/TP router, and BACnet/SC client access through a Secure Connect hub.
German documentation is available here: README.de.md.
Supported transports
| Transport | Support | Notes |
| --- | --- | --- |
| BACnet/IP | Client and server | Uses UDP, default port 47808. |
| BACnet MS/TP | Via external router/gateway | The adapter communicates BACnet/IP to a router that bridges to RS-485 MS/TP. Direct serial token-passing MS/TP is not implemented in this JavaScript adapter. |
| BACnet/SC | Client reads/writes | Uses a BACnet/SC hub URL such as wss://192.168.2.50:47809. Server mode is not available for BACnet/SC yet. |
Requirements
- ioBroker with js-controller 6 or newer.
- Node.js 22 or newer.
- BACnet/IP network access for BACnet/IP and MS/TP-router mode.
- For MS/TP: a configured BACnet/IP-to-MS/TP router or gateway connected to the RS-485 bus.
- For BACnet/SC: a reachable BACnet/SC hub and valid WebSocket/TLS trust configuration on the host.
Client mode
For one BACnet/IP device, configure:
clientTargetIp: IP address of the BACnet/IP device or MS/TP router targetclientTargetDeviceId: optional BACnet device IDclientObjectsJson: objects to read from that target
Example for clientObjectsJson:
[
{ "id": "temp", "name": "Supply temperature", "type": "analogValue", "instance": 1, "write": false },
{ "id": "enable", "name": "Enable", "type": "binaryValue", "instance": 2, "write": true }
]For multiple BACnet/IP devices, configure clientDevicesJson as an advanced array:
[
{
"id": "ahu1",
"name": "AHU 1",
"address": "192.168.2.50",
"deviceId": 12345,
"objects": [
{ "id": "temp", "name": "Supply temperature", "type": "analogValue", "instance": 1, "write": false },
{ "id": "enable", "name": "Enable", "type": "binaryValue", "instance": 2, "write": true }
]
}
]Client values are created below:
bacnet-flex.0.client.<device>.<object>Writable BACnet objects also get a _set state. Writes are sent as WriteProperty presentValue.
BACnet MS/TP
MS/TP is a serial RS-485 field bus with token passing. This adapter does not implement direct serial MS/TP framing. Use an external BACnet/IP-to-MS/TP router or gateway and select transport BACnet MS/TP via BACnet/IP router.
Typical setup:
- Connect the MS/TP devices to a BACnet/IP-to-MS/TP router.
- Configure baud rate, MAC address, max master and network number on the router.
- Put the router IP into
MS/TP router IP. - Configure the target objects manually or use discovery if the router exposes the devices correctly.
BACnet/SC
BACnet/SC mode connects as a BACnet/SC thin client to a Secure Connect hub.
Configure:
Transport:BACnet/SC clientBACnet/SC hub URL: for examplewss://192.168.2.50:47809BACnet/SC device UUID: optional persistent local UUID
BACnet/SC mode currently supports client reads, writes and Who-Is/I-Am collection. Server mode is disabled in BACnet/SC mode.
Server mode
Server mode is available for BACnet/IP transport. Configure serverStatesPattern to select ioBroker states. Number states are published as analogValue, boolean states as binaryValue, and all other states as characterStringValue.
The BACnet server answers:
Who-IsReadPropertyReadPropertyMultipleWritePropertyforpresentValueon writable published objects
Additional manual server data points can be configured in the Admin table serverPoints. Each row defines the BACnet object type and instance that a BACnet client can read from this adapter.
If a row has no stateId, the adapter creates an ioBroker state below:
bacnet-flex.0.server.points.<instance>If stateId is set, that existing ioBroker state is exposed as the BACnet object. Set writable to allow BACnet WriteProperty presentValue writes for that row.
Troubleshooting
No BACnet/IP devices found
- Check local firewall rules for UDP port
47808. - Set the correct broadcast address for the subnet.
- Try a specific local bind interface instead of
0.0.0.0.
MS/TP devices are not visible
- Check the router configuration first: baud rate, MAC address, max master and network number.
- Verify that the BACnet/IP side of the router is reachable.
- Some routers do not forward all discovery broadcasts; configure objects manually if needed.
BACnet/SC does not connect
- The hub URL must start with
wss://. - Check TLS trust and certificates on the host.
- Check that the Secure Connect hub accepts this client.
Changelog
0.1.3
- Clean release metadata after the 0.1.2 workflow release.
0.1.2
- Add package and integration smoke tests for the release workflow.
0.1.1
- Add release metadata, German documentation and checker-compatible repository setup.
0.1.0
- Initial BACnet Flex adapter with BACnet/IP client/server, MS/TP router mode and BACnet/SC client mode.
Older entries are stored in CHANGELOG_OLD.md.
License
MIT
Copyright (c) 2026 TheBam1990