iobroker.heatpump-modbus
v0.0.3
Published
Community adapter for compatible heat pumps using Modbus RTU
Readme
ioBroker Heat Pump Modbus Adapter
Independent community adapter for local monitoring and control of compatible heat pumps using Modbus RTU.
Developed and maintained by Helge Kaiser.
Current compatibility
The adapter was developed and tested on real hardware with:
- SWD WP6 R290
- Modbus RTU
- transparent TCP-to-RS485 gateway
The register mapping and write behaviour are based on the available Modbus documentation and verified against the real bus traffic of the tested system.
The current profile maps 58 Modbus register addresses:
- 41 read-only register addresses
- 17 read/write register addresses
Several registers contain multiple flags or logical states, so the number of ioBroker states is higher than the number of physical Modbus registers.
Heat pumps using the same or a closely related controller and Modbus protocol may also work. Compatibility with other devices is not guaranteed until verified on real hardware.
Reports about additional compatible models and firmware versions are welcome.
Independent project
This is an independent open-source community project.
It is not an official product of SWD, Power World, or any other heat-pump manufacturer and is not affiliated with, endorsed by, or supported by those manufacturers.
Manufacturer and product names are mentioned only to describe tested or potentially compatible hardware.
Operating principle
The adapter is designed primarily as a passive Modbus RTU listener.
The heat-pump controller already continuously exchanges Modbus data on its internal RS485 bus. The adapter uses these existing telegrams instead of generating periodic read requests itself.
Therefore:
- no active polling is performed by the adapter
- no fallback polling is used
- valid passive register values are processed immediately
- ioBroker states are only updated when their decoded value changes
info.connectionis based on receiving valid Modbus traffic
This minimizes additional traffic on the existing controller bus.
Connection
The adapter supports two Modbus RTU connection methods.
TCP/IP to RS485 gateway
This is the currently verified connection method.
The gateway must operate as a transparent TCP-to-RS485 serial server.
Required settings:
- TCP Server mode
- 9600 baud
- 8 data bits
- parity: none
- 1 stop bit
- flow control: none
- protocol: none / transparent
The adapter sends and receives complete Modbus RTU frames including CRC.
Do not enable Modbus TCP-to-RTU protocol conversion.
A Waveshare Ethernet-to-RS485 gateway has been used successfully during development and is therefore a tested example. Equivalent transparent TCP-to-RS485 gateways should also work.
For the tested Waveshare setup, an RS485 Conflict Time Gap of 5 ms is used.
USB / Serial
Direct USB-to-RS485 adapters are supported through a Linux serial device, for example:
/dev/ttyUSB0
or
/dev/ttyACM0
The serial parameters are fixed:
- 9600 baud
- 8 data bits
- parity: none
- 1 stop bit
- no flow control
USB / Serial support is implemented but has not been tested as extensively as the transparent TCP connection.
Safety and liability
[!CAUTION] USE AT YOUR OWN RISK.
This adapter communicates with heating equipment and can modify operating modes, temperatures, pump parameters and other device settings.
Incorrect wiring, configuration, incompatible hardware, software errors or unintended write operations may cause malfunction, loss of heating or hot water, overheating, increased energy consumption, damage to the heat pump or connected equipment and, in extreme cases, consequential damage including fire, property damage, serious injury or death.
No guarantee is given for compatibility, correctness, availability or safe operation with any particular installation.
The software is provided "as is", without warranty. Use is at your own risk. Liability is limited to the maximum extent permitted by applicable law.
Manufacturer documentation, electrical safety regulations and all protective functions of the heat pump always take precedence over this documentation. Electrical work and modifications to heating equipment must only be carried out by suitably qualified persons.
RS485 connection
[!WARNING] Do not assume that every RS485 connector in the heat pump carries the same bus.
The connection described below is the internal RS485 bus observed on the tested SWD WP6 R290 built in 2026.
Wiring, connector type and signal assignment may differ on other production years, controller revisions or related heat-pump models.
Main controller connection
On the tested SWD WP6 R290 built in 2026, the internal RS485 connection is available at the main controller connector shown below.

The tested wiring uses:
- Yellow and green: the two RS485 data lines
- Black: GND
- GND was not required for successful operation in the tested installation
The exact assignment of yellow/green to A/B is intentionally not specified here.
Verify the A/B assignment on the particular unit before connecting the adapter.
Do not rely solely on wire colours because wiring may differ between production revisions.
Internal cable splice / service connector
On the tested unit there is also an internal splice in the cable harness leading to the connector shown below. The RS485 data lines can be accessed there.

This arrangement was observed on an SWD WP6 R290 built in 2026.
It may not exist, or may be wired differently, on other production versions.
Bus and write safety
Passive monitoring itself does not transmit anything to the Modbus bus.
A transmission is only generated when an ioBroker state marked as writable is changed with ack=false.
Writes are deliberately conservative:
- only one Modbus write is active at a time
- queued changes for the same state keep only the newest requested value
- if the last passively observed device value already equals the requested value, no write is sent
- the adapter waits for at least 200 ms of bus inactivity before transmitting
- writable registers are sent using Modbus function code 06
- after a write, confirmation is obtained from the following passive device traffic
- up to the next two passive observations of the affected register are accepted as confirmation
- if the device has not accepted the value, the write may be retried
- a maximum of three actual write attempts is made
ack=trueis only set after the requested value has been observed passively from the device- after final failure, the last passively observed real device value is restored in ioBroker
For registers containing several bit flags, unrelated bits are preserved using the latest passively observed raw register value.
Main control states
R means read-only.
RW means read and write.
[!WARNING] Writable states directly influence the heat pump. Only use them when the connected model and register mapping have been verified.
| Address | State | Access | Description | Values / range |
| -------- | ------------------------ | :----: | ----------------------------- | ---------------------------------------------------------------------- |
| 0x003F | device.power | RW | Heat-pump controller power | true, false |
| 0x0040 | frequencyMode.setpoint | RW | Compressor operating strategy | smart, silent, powerful |
| 0x0041 | vacation.enabled | RW | Vacation mode | true, false |
| 0x0043 | operatingMode.setpoint | RW | Operating mode | hotWater, heating, cooling, hotWaterHeating, hotWaterCooling |
| 0x00BE | hotWater.setpoint | RW | Domestic hot-water setpoint | 28–60 °C |
| 0x00BF | cooling.setpoint | RW | Cooling setpoint | 7–30 °C |
| 0x00C0 | heating.setpoint | RW | Heating setpoint | 15–50 °C |
| 0x00D0 | vacation.setpoint | RW | Vacation temperature setpoint | 15–50 °C |
Water-pump controls
The following controller parameters are exposed as writable states.
| Address | State | Access | Description | Values / range |
| -------- | ------------------------------- | :----: | ------------------------------- | ------------------------------------ |
| 0x015B | pump.constantTemperatureMode | RW | Constant-temperature pump mode | intermittent, continuous, stop |
| 0x015C | pump.constantTemperatureCycle | RW | Constant-temperature pump cycle | 1–120 min |
| 0x015F | pump.mode | RW | DC water-pump mode | disabled, automatic, manual |
| 0x0160 | pump.adjustmentCycle | RW | Pump adjustment cycle | 10–100 s |
| 0x0161 | pump.manualSpeed | RW | Manual pump speed | 10–100 % |
| 0x0162 | pump.maxSpeed | RW | Maximum pump speed | %, controller-specific range |
| 0x0163 | pump.minSpeed | RW | Minimum pump speed | 10–100 % |
| 0x0164 | pump.adjustmentStep | RW | Pump adjustment speed | controller-specific range |
| 0x0165 | pump.pwmFrequencyType | RW | PWM input frequency type | controller-specific value |
For pump.maxSpeed, pump.adjustmentStep and pump.pwmFrequencyType, the available Modbus documentation identifies the registers as writable but does not provide a reliable value range or enum definition.
The adapter therefore does not invent undocumented limits or enum meanings for those values.
Constant-temperature pump operation (F02 / F03)
The heat-pump controller provides two parameters that define how the water pump behaves after the requested constant temperature has been reached.
These parameters are separate from pump.mode (F04).
F02 - Water pump constant-temperature operation mode
State:
pump.constantTemperatureMode
Register:
0x015B
The available modes are:
| Raw value | State value | Behaviour |
| :-------: | -------------- | ----------------------------------------------------------------------------- |
| 0 | intermittent | Pump operates intermittently after the requested temperature has been reached |
| 1 | continuous | Pump continues running after the requested temperature has been reached |
| 2 | stop | Pump stops after the requested temperature has been reached |
In other words:
- Intermittent: the pump is periodically restarted after reaching the target temperature.
- Continuous: the pump continues to run even after the target temperature has been reached.
- Stop: the pump stops when the target temperature has been reached.
F03 - Water pump constant-temperature cycle
State:
pump.constantTemperatureCycle
Register:
0x015C
Range:
1–120 min
F03 is relevant when F02 is set to intermittent.
According to the manufacturer description, for example:
F03 = 15
means:
- pump OFF for 15 minutes
- pump ON for 3 minutes
- the cycle is then repeated as required by the controller
Observed values on the tested SWD WP6 R290
The following values have been observed passively on the real Modbus bus:
0x015B = 1->continuous0x015C = 15-> 15-minute intermittent cycle setting
The value of F03 remains stored even when F02 is currently set to
continuous. It only becomes relevant for pump operation when F02 is changed
to intermittent.
[!IMPORTANT] F02 and F03 must not be confused with
pump.mode.
pump.modeis F04 / register0x015Fand controls the basic DC water-pump mode:
disabledautomaticmanualF02/F03 instead define what the pump should do when the requested constant temperature has been reached.
Temperature states
| State | Access | Description | Unit |
| ----------------------------------- | :----: | ---------------------------------------- | ---- |
| temperature.inlet | R | Inlet water temperature / return | °C |
| temperature.outlet | R | Outlet water temperature / flow | °C |
| temperature.tank | R | Water-tank temperature | °C |
| temperature.outside | R | Outside temperature | °C |
| temperature.suctionGas | R | Suction-gas temperature | °C |
| temperature.evaporator | R | External-coil / evaporator temperature | °C |
| temperature.innerCoil | R | Inner-coil temperature | °C |
| temperature.exhaustGas | R | Discharge / exhaust-gas temperature | °C |
| temperature.heatSink | R | Inverter heat-sink temperature | °C |
| temperature.lowPressureConversion | R | Temperature calculated from low pressure | °C |
Compressor, fan and pump monitoring
| State | Access | Description | Unit |
| ---------------------------- | :----: | -------------------------------------------------- | ---- |
| compressor.frequency | R | Actual compressor frequency | Hz |
| compressor.targetFrequency | R | Compressor target frequency reported by controller | Hz |
| compressor.current | R | Compressor current | A |
| fan.speed1 | R | Fan 1 speed | rpm |
| fan.speed2 | R | Fan 2 speed | rpm |
| pump.speed | R | Actual water-pump speed | % |
| pump.targetSpeed | R | Water-pump target speed reported by controller | % |
pump.targetSpeed is not necessarily the actual physical pump speed.
For example, the controller may report a target of 100 % while pump.speed reports a considerably lower actual speed.
Performance values
The following performance values were verified on the tested SWD WP6 R290 by correlation with real operating data:
| State | Address | Access | Conversion |
| ---------------------- | :------: | :----: | ---------- |
| performance.capacity | 0x0036 | R | raw × 2 W |
| performance.cop | 0x0037 | R | raw ÷ 10 |
performance.capacity represents the heating/cooling capacity reported by the
controller.
performance.cop represents the reported COP/EER.
Several real operating points showed close agreement between the reported capacity, hydraulic heat output, electrical power and COP.
[!NOTE] The mapping is verified on the tested SWD WP6 R290. Compatibility and scaling should still be confirmed on other controller revisions or heat-pump models.
Hydraulic, pressure and electrical values
| State | Access | Description | Unit |
| -------------------------- | :----: | ---------------------------------------- | ---- |
| water.flow | R | Water flow | m³/h |
| pressure.low | R | Refrigerant low pressure | bar |
| expansionValve.main | R | Main electronic expansion-valve position | P |
| expansionValve.auxiliary | R | Auxiliary expansion-valve position | P |
| electrical.dcBusVoltage | R | DC bus voltage | V |
| electrical.voltage | R | Supply voltage | V |
| electrical.current | R | Supply current | A |
| electrical.power | R | Compressor operating power | W |
| electrical.totalPower | R | Total operating power | W |
Output states
These states report controller output requests.
They do not independently prove that the connected component is electrically energized or operating correctly.
| State | Access | Description |
| --------------------------- | :----: | ----------------------------------------------- |
| output.compressor | R | Compressor output |
| output.fanMotor | R | Fan-motor output |
| output.fourWayValve | R | Refrigerant four-way-valve output |
| output.chassisHeater | R | Chassis / base-heater output |
| output.acElectricHeater | R | Additional space-heating electric-heater output |
| output.threeWayValve | R | Hydraulic three-way-valve output |
| output.tankElectricHeater | R | Domestic hot-water tank electric-heater output |
| output.circulationPump | R | Circulation-pump output |
| output.crankcaseHeater | R | Compressor crankcase-heater output |
Faults and diagnostics
The adapter passively evaluates the documented controller fault registers:
0x0007through0x000D0x001F0x0020
Known documented fault bits are translated into fault codes and readable descriptions.
Undocumented inverter fault values are deliberately kept as raw values instead of assigning speculative meanings.
| State | Access | Description |
| ---------------------------------- | :----: | --------------------------------------------------- |
| status.defrosting | R | Defrost cycle active |
| fault.active | R | At least one detected fault is active |
| fault.codes | R | Active documented fault codes / raw inverter faults |
| fault.messages | R | Human-readable fault information |
| diagnostics.rawWorkingStatus | R | Raw controller working-status word |
| diagnostics.rawOutputFlags1 | R | Raw output-flags word 1 |
| diagnostics.rawOutputFlags2 | R | Raw output-flags word 2 |
| diagnostics.rawOutputFlags3 | R | Raw output-flags word 3 |
| diagnostics.rawFaultFlag1 | R | Raw fault register 0x0007 |
| diagnostics.rawFaultFlag2 | R | Raw fault register 0x0008 |
| diagnostics.rawFaultFlag3 | R | Raw fault register 0x0009 |
| diagnostics.rawFaultFlag4 | R | Raw fault register 0x000A |
| diagnostics.rawFaultFlag5 | R | Raw fault register 0x000B |
| diagnostics.rawFaultFlag6 | R | Raw fault register 0x000C |
| diagnostics.rawFaultFlag7 | R | Raw fault register 0x000D |
| diagnostics.rawInverterFaultLow | R | Raw inverter fault register 0x001F |
| diagnostics.rawInverterFaultHigh | R | Raw inverter fault register 0x0020 |
| diagnostics.rawFaultFlags | R | Combined raw fault-register overview |
Adapter status
| State | Access | Description |
| ----------------- | :----: | -------------------------------------- |
| info.connection | R | Valid Modbus traffic is being received |
Additional registers
The controller exposes many additional service and protection parameters.
Only registers with a sufficiently understood and useful meaning are mapped. Potentially unsafe or insufficiently documented service settings are intentionally not exposed.
Still to be verified include:
- SG / Smart Grid signal
- EVU / external utility control
- additional service and protection parameters
Compatibility reports
If another heat pump uses the same controller or Modbus register layout, please report:
- manufacturer
- model
- controller / firmware version
- which readings work
- which writable functions were successfully tested
This will allow confirmed compatibility information to be added later.
Changelog
0.0.3
- Added passive heating/cooling capacity monitoring at
0x0036 - Added passive COP/EER monitoring at
0x0037 - Capacity and COP/EER mapping verified by correlation with real operating data on the tested SWD WP6 R290
- Improved package test configuration for release checks
0.0.2
Added F02/F03 constant-temperature circulation pump control with intermittent, continuous and stop modes and configurable cycle.
Reworked adapter around passive Modbus RTU monitoring
Removed active polling and fallback polling
Simplified write handling
Writes wait for at least 200 ms of bus inactivity
Serialized write queue with newest-value replacement for queued states
Passive write confirmation using up to two subsequent observations
Maximum of three write attempts
Added writable vacation temperature setpoint
Added writable DC water-pump controls
0x015B,0x015Cand0x015Fthrough0x0165Corrected
pump.adjustmentCyclerange to 10–100 secondsAdded passive fault-register monitoring and fault states
Added raw fault diagnostics
Preserved unrelated bits for writable shared-bit registers
Added unsigned 16-bit validation for unrestricted numeric writes
0.0.1
- Initial public version
- Modbus RTU communication via transparent TCP-to-RS485 gateway
- Experimental direct USB-to-RS485 support
- Initial monitoring and control support for the tested SWD WP6 R290
- RS485 connection and safety documentation