iobroker.remko
v0.4.0
Published
Read and control REMKO heat pumps (Smart-Web / Smart-Control) via local MQTT
Readme

ioBroker.remko
Tests:
REMKO heat pump adapter for ioBroker
Reads and controls REMKO heat pumps with Smart-Web / Smart-Control (firmware 4.26 and newer) locally via MQTT. No cloud and no additional MQTT broker needed.
Tested with: REMKO WKF 100, Smart-Web firmware 4.28. Feedback on other models (WKF, WSP, LWM, KWT …) is very welcome – please open an issue.
Manufacturer: REMKO GmbH & Co. KG
Disclaimer: This project is not affiliated with, endorsed by or supported by REMKO GmbH & Co. KG. REMKO is a trademark of its respective owner. Use at your own risk.
How it works
The Smart-Control runs its own MQTT broker (WebSocket port 9001, which is also used by the web UI, and TCP port 1883). On startup the adapter reads everything it needs directly from the web UI of the heat pump:
| Source | Content |
|---|---|
| /js/smt.min.js | firmware version → topic (e.g. V04P28/SMTID), MQTT credentials |
| /json/smt18.json + /json/smtmain.json | complete register database (~2,150 registers): type, range, decimals, unit, texts, menu tree, display conditions |
No register is hard-coded – other models and firmware versions bring their own definitions.
Protocol:
- read:
CLIENT2HOST←{"FORCE_RESPONSE":true,"query_list":[1082,5039,…],"CLIENT_ID":"SMT123I0000000000000000"} - answer:
HOST2CLIENT→{"values":{"1082":"01C2","5039":"01DC",…}}(big-endian hex, scaled according to the register database) - write: the same request with
"values":{"1082":"01E0"}
Configuration
| Option | Description | |---|---| | IP address | IP address of the Smart-Web / Smart-Control | | Transport / port | WebSocket 9001 (default, like the web UI) or MQTT TCP 1883 | | MQTT password / topic | leave empty – read automatically from the web UI | | Fast query / full refresh | interval of the fast query (overview values) and of the full refresh of all registers | | Which data points | like the web UI (user, status, overview) or additionally service / expert / commissioning | | Writable registers | off, user menu (recommended) or all parameters (expert) |
Objects
The adapter evaluates the display conditions of the web UI (e.g. "solar only if a solar system is enabled"), so only data points that exist on your installation are created. The structure follows the menu of the controller:
remko.0.information.<area>.<no>– user → information (e.g.information.warmwasser.5039)remko.0.einstellungen.<area>.<no>– user → settings (e.g.einstellungen.warmwasser.1082)remko.0.status.<no>– status pageremko.0.uebersicht…,remko.0.homescreen…– basic display- optional
service…,experte…,inbetriebnahme…
The register number is always the last part of the id. Names, units, min/max and enumerations (common.states) come from the heat pump (German texts, as delivered by the controller).
Important registers (WKF 100):
| No | Meaning | |---|---| | 1079 | DHW mode (0 comfort, 1 eco, 2 solar/PV only, 3 off) | | 1082 | DHW setpoint | | 1951 / 1088 | room climate mode | | 1893 / 1894 | absence / party | | 1946 | colder / warmer | | 5693 | 1x DHW heating (button) | | 1269 / 1270 | DHW setpoint SG-Ready state 3 / 4 | | 1902 / 1258 | heating setpoint SG-Ready state 3 / 4 | | 2142, 1719–1722, 1679, 2164 | PV self-consumption / influence | | 5001 | current operating mode | | 5032 / 5039 / 5132 / 5581 | outdoor / DHW actual / flow / return temperature | | 5320 / 5321 | electrical / thermal power | | 5105 / 5119 | electrical / thermal energy | | 5359 / 5565 | PV power / PV yield (from the heat pump's meter input) | | 5174 / 5572 | utility lock / remaining lock time |
Write protection
- Off: read only
- User menu (default): only registers that can also be changed in the user menu of the controller. Network, password and installation registers are always locked. Actions: only "1x DHW heating" and "reset fault".
- All parameters: expert mode – also service/installation values and critical actions (update, restart, reset). Use with care!
Values outside the allowed range are rejected by the adapter.
Test without installation
node tools/probe.js <ip-of-heat-pump> # read only
node tools/probe.js <ip-of-heat-pump> --write 1082=46 # write one valueDonate
If you like this adapter and want to support its development, you can buy me a coffee:
Credits
Protocol knowledge partly based on Altrec/remko_mqtt-ha, fuchsi585/remko_http and Christoph-87/remko-smartweb-ha.
Changelog
0.4.0 (2026-09-30)
- (mrdimixx) object structure fixed (ioBroker object checker): only valid roles (
value/levelinstead ofvalue.mode/level.mode), writable power settings uselevel - (mrdimixx) actions are write-only buttons (
read: false); actions that are not allowed are no longer created - (mrdimixx) object names in all ioBroker languages (texts from the controller, English as fallback)
- (mrdimixx) existing objects are replaced on update so outdated attributes disappear (user settings like history are kept)
0.3.3 (2026-09-30)
- (mrdimixx) registers containing secrets (service/expert passwords, session id, unlock code, SMT-ID) are no longer read or created; existing objects are removed automatically
0.3.2 (2026-09-28)
- (mrdimixx) PayPal donation link added (README, GitHub sponsor button, npm funding)
0.3.1 (2026-09-28)
- (mrdimixx) release via GitHub Actions (npm trusted publishing with provenance)
0.3.0 (2026-09-28)
- (mrdimixx) prepared for the ioBroker repository: English README, translations, tests, GitHub Actions, npm deployment
- (mrdimixx) log messages in English
0.2.1 (2026-09-28)
- (mrdimixx) actions (e.g. 5693 "1x DHW heating", 2126 "reset fault") as buttons; critical actions only in write mode "all"
- (mrdimixx) role of the coefficient of performance fixed
0.2.0 (2026-09-28)
- (mrdimixx) only registers that are also shown by the web UI (display conditions)
- (mrdimixx) objects structured by menu; old 0.1 objects are removed automatically
Older changes can be found in CHANGELOG_OLD.md.
License
MIT License
Copyright (c) 2026 mrdimixx [email protected]
Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the Software without restriction, including without limitation the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies of the Software, and to permit persons to whom the Software is furnished to do so, subject to the following conditions:
The above copyright notice and this permission notice shall be included in all copies or substantial portions of the Software.
THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.