iobroker.solintec
v0.1.0
Published
ioBroker adapter for Solinteg MHT-25~50K-100 hybrid inverters with Dyness STACK100 battery, via local Modbus TCP.
Readme

ioBroker.solintec
Reads PV, grid/meter and battery data from a Solinteg MHT-25~50K-100 hybrid inverter (25-50 kW, three-phase) with a Dyness STACK100 battery (51.2 kWh, connected to the inverter via CAN/RS485) over local Modbus TCP. No cloud account, no internet access required.
Table of contents
- Why this adapter?
- Register source and limitations (please read)
- Installation
- Configuration
- Object/state structure
- EMS write access (controlling the inverter/battery)
- Polling and efficient reads
- Security & privacy
- Development
- Changelog
- License
Why this adapter?
There is no generic "Solinteg" support in ioBroker. The Solinteg WR speaks openly documented Modbus TCP, so it could in principle be read out with the generic ioBroker.modbus adapter and a manually entered register list - but that means re-entering 50+ registers by hand in the admin UI, with no code-level control over scaling, data types or object structure. This adapter instead talks Modbus TCP directly (via modbus-serial), the same way ioBroker.zeptrion, ioBroker.goodwe-sems and ioBroker.husqvarna-automower-connect each talk directly to their respective device/cloud API, giving full control over register mapping, scaling and the resulting object tree - plus the option to actively control the inverter/battery (EMS write access, off by default).
Register source and limitations (please read)
Register addresses in lib/registers.js are sourced from the official Solinteg Modbus TCP protocol documentation, cross-checked against wills106/homeassistant-solax-modbus (custom_components/solax_modbus/plugin_solinteg.py), which documents the identical INTEG-M register family also used by Wattsonic and M-TEC Energy Butler rebrands.
These addresses have not yet been verified against real hardware. Before relying on this adapter, check the first poll's results carefully, in particular:
- Byte/word order for
u32/s32registers (PV power, AC power, battery power, energy totals) - The exact location and effect of the EMS control registers (
50xxx/52xxxblock) before enabling EMS write access
Dyness battery cell-level detail beyond min/max cell voltage (16 individual cell voltages per module) is not available over Modbus at the inverter - only min/max cell voltage and their cell IDs are exposed there. Full per-cell detail requires the separate Dyness Cloud API/MQTT (ems.dyness.com Developer Center), which this adapter does not implement.
Installation
Once this adapter is listed in the official ioBroker adapter repository, install it the normal way: Admin -> Adapters -> search for "solintec" -> install.
Until then, an ioBroker administrator can add it manually on the ioBroker host:
iobroker url iobroker.solintecConfiguration
| Tab | Setting | Description | | --- | --- | --- | | Connection | Host / IP address | IP or hostname of the inverter (or Modbus TCP/RTU gateway) | | Connection | Port | Modbus TCP port, usually 502 | | Connection | Unit ID | Modbus slave/unit ID, usually 1 | | Connection | Request timeout | Timeout per Modbus request, in seconds | | Polling | Fast poll interval | How often power/flow values (PV, grid, battery) are read (default 5s) | | Polling | Slow poll interval | How often energy counters and diagnostics are read (default 30s) | | EMS control | Enable EMS write access | Off by default - see EMS write access |
Object/state structure
solintec.0.info.connection Inverter reachable (bool)
solintec.0.info.lastSuccess Timestamp of the last successful poll
solintec.0.info.lastError Last error message
solintec.0.info.serialNumber / .firmwareVersion
solintec.0.diag.inverterStatus / .faultFlags1-3 / .radiatorTemperature
solintec.0.pv.string1-4.voltage / .current / .power
solintec.0.pv.totalPower
solintec.0.grid.acPower / .frequency
solintec.0.grid.voltageL1-3 / .currentL1-3
solintec.0.meter.power / .powerL1-3
solintec.0.meter.gridImportTotal / .gridExportTotal
solintec.0.battery.voltage / .current / .power / .soc / .soh / .temperature
solintec.0.battery.minCellVoltage / .maxCellVoltage (+ their cell IDs)
solintec.0.battery.chargeLimit / .dischargeLimit
solintec.0.battery.chargeToday / .chargeTotal / .dischargeToday / .dischargeTotal
solintec.0.battery.manufacturer / .ratedCapacity
solintec.0.energy.pvGenerationToday / .pvGenerationTotal
solintec.0.energy.houseConsumptionToday / .houseConsumptionTotal
solintec.0.ems.* EMS control registers, see belowAll PV/grid/meter/battery power-flow states are polled at the fast interval; energy counters, diagnostics and EMS registers are polled at the slow interval.
EMS write access (controlling the inverter/battery)
The ems.* states (working mode, charge/discharge power target, import/export limits, battery SOC protection limits, ...) are always read, so you can see the inverter's current EMS configuration regardless of this setting. Writing to them is disabled by default: any attempted write is logged and ignored until "Enable EMS write access" is turned on in the instance configuration.
Only enable this if you actively want to control the inverter/battery (e.g. schedule charge/discharge power, cap grid export). Getting a register or scaling wrong here can put the inverter into an unintended operating mode - see Register source and limitations.
Polling and efficient reads
lib/blocks.js merges adjacent (or near-adjacent, small-gap) registers into as few readHoldingRegisters() calls as possible per poll cycle, instead of one Modbus request per register. Fast-group and slow-group registers are blocked independently and polled on their own interval.
Security & privacy
- The adapter performs Modbus TCP against a device on your local network - no cloud account, no external API, no credentials to store.
- EMS write access (the only functionality that can change the inverter's behavior) is disabled by default and must be explicitly enabled.
- Written values are range-checked against each register's documented min/max before being sent.
Development
npm install
npm run lint
npm test # unit tests (lib/registers.js, lib/modbusClient.js, lib/blocks.js) + package consistency checkRecommended additionally before every release:
npx @iobroker/repochecker@latest .Pull requests are welcome, especially to verify/correct register addresses against real hardware, or to improve translations (currently English/German are complete; the other 9 languages use English text as a placeholder).
Changelog
0.1.0 (2026-08-15)
- Initial release: reads PV, grid/meter and battery values from a Solinteg MHT-25~50K-100 hybrid inverter (Dyness STACK100 battery via CAN/RS485) over local Modbus TCP. Optional EMS write access is disabled by default.
License
MIT License
Copyright (c) 2026 Stefan Bühler
Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the Software without restriction, including without limitation the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies of the Software, and to permit persons to whom the Software is furnished to do so, subject to the following conditions:
The above copyright notice and this permission notice shall be included in all copies or substantial portions of the Software.
THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.