node-red-contrib-heat-curve
v1.0.1
Published
Node-RED heating curve node - calculates flow temperature setpoint based on outdoor temperature
Maintainers
Readme
node-red-contrib-heat-curve
Node-RED Heating Curve Node - calculates flow temperature setpoint based on outdoor temperature (Heizkurve).
Features
- Configurable heating curve with slope or design mode
- Night setback (Nachtabsenkung)
- Summer lockout (Sommerabschaltung)
- Two outputs: Flow temp + Heating active boolean
- Min/max flow temperature limits
- Runtime overrides via message properties
Formula
flowTemp = roomTemp + slope × (roomTemp - outdoorTemp) + shift
With setback: flowTemp = flowTemp - setbackDeltaOutputs
- Output 1: Flow temperature setpoint (°C) or
nullif summer lockout - Output 2: Heating active boolean (
true= heating,false= summer lockout)
Example
slope=1.0, roomTemp=20, shift=0:
Outdoor -10°C → Flow 50°C
Outdoor 0°C → Flow 40°C
Outdoor 10°C → Flow 30°C
With setback (delta=10K):
Outdoor -10°C → Flow 40°C (50-10)
Summer lockout (threshold=18°C):
Outdoor 20°C → Output 1: null, Output 2: falseConfiguration
| Property | Description | Default | Range | |----------|-------------|---------|-------| | Mode | Slope or Design | slope | - | | Slope | Curve steepness | 1.0 | 0.2–3.0 | | Design Outdoor | Design outdoor temp | -15 | - | | Design Flow | Design flow temp | 55 | - | | Room Temp | Room setpoint | 20 | - | | Shift | Parallel shift (Niveau) | 0 | -15 to +15 | | Min Flow | Minimum flow temp | 20 | - | | Max Flow | Maximum flow temp | 75 | - | | Setback Delta | Night setback reduction | 10 | 0–30 K | | Summer Lockout | Lockout threshold | 18 | - | | Decimals | Decimal places | 1 | 0–2 |
Input
msg.payload- Outdoor temperature in °Cmsg.setback-trueto activate night setback
Runtime Override
All configuration values can be overridden via msg properties. Setback state is retained until explicitly changed.
| Property | Description |
|----------|-------------|
| msg.setback | Activate night setback (sticky) |
| msg.setbackDelta | Override setback delta |
| msg.summerLockout | Override summer lockout threshold |
| msg.slope | Override slope |
| msg.designOutdoor | Override design outdoor temp |
| msg.designFlow | Override design flow temp |
| msg.roomTemp | Override room setpoint |
| msg.shift | Override shift |
| msg.minFlow | Override min flow temp |
| msg.maxFlow | Override max flow temp |
Output
Output 1:
{
"payload": 50.0,
"heatCurve": {
"outdoorTemp": -10,
"flowTemp": 50.0,
"slope": 1.0,
"roomTemp": 20,
"shift": 0,
"minFlow": 20,
"maxFlow": 75,
"clamped": false,
"clampedAt": null,
"setback": false,
"setbackDelta": 10,
"flowTempBeforeSetback": 50.0,
"summerLockout": 18,
"heatingActive": true
}
}Output 2:
{
"payload": true
}Node Status
- -10°C → 50.0°C - Normal heating
- -10°C → 40.0°C (setback) - Night setback active
- 20°C → locked out - Summer lockout
- -20°C → 75.0°C (clamped max) - Clamped to limit
Use Cases
| Application | Description | |-------------|-------------| | HVAC | Heating system control | | Building Automation | Weather-compensated heating | | Heat Pump | Flow temperature optimization | | Night Mode | Reduced heating at night |
Author
sr.rpo
License
MIT